The grey transformer on a pole or plinth at the end of your street feeds a few dozen homes. A typical one is rated 250 kVA, which means about 333 A from each of its low-voltage terminals at full load. If those terminals were shorted, the current would not be infinite, and it would not be 333 A either. It would be about 7,400 A, more than 22 times full load. One number on the transformer's nameplate tells you this: its per-cent impedance.
What limits the current when a transformer is short-circuited?
You already know the answer for a cell. A cell of emf E and internal resistance r, shorted by a thick wire, gives a current of E ÷ r, as worked in cells, EMF and internal resistance. Why a short does not draw an infinite current in the first place is explained in what happens in a short circuit.
A transformer behaves the same way. Think of it as an ideal transformer, which changes the voltage perfectly, followed by a small impedance in series with its output. That impedance comes from two things:
the resistance of the copper windings, and
the leakage reactance, from the part of each winding's magnetic flux that does not link the other winding.
When the output is shorted, this internal impedance is the only thing left to limit the current. It plays the part of r.
What does "4.5% impedance" on a nameplate mean?
Engineers do not usually quote this impedance in ohms. They quote it as a percentage, found by a factory test.
Short the low-voltage terminals together.
Apply a voltage to the high-voltage side, starting from zero.
Raise it slowly until the current in the windings reaches the full-load value.
The voltage needed, as a percentage of the rated voltage, is the per-cent impedance.
Rex Power Magnetics, a transformer maker, describes exactly this in its note on how to calculate transformer fault current: short the secondary and raise the primary voltage until full-load current flows; that voltage as a percentage of rated voltage is the impedance. The same note gives the fault current at the terminals as full-load current divided by the per-unit impedance (the percentage ÷ 100).
The logic is simple proportion. If 4.5% of the rated voltage drives full-load current through the internal impedance, then the full 100% drives 100 ÷ 4.5 = 22.2 times full-load current.
For India, the Bureau of Indian Standards' summary of IS 1180 for distribution transformers lists a recommended impedance of 4.5% at 75 °C for ratings from 16 kVA up to 630 kVA, 5% from 800 to 1,250 kVA, and 6.25% from 1,600 to 2,500 kVA.
Worked example: what fault current can a 250 kVA transformer give?
Take a three-phase 250 kVA, 11 kV/433 V distribution transformer with 4.5% impedance, the IS 1180 value for this rating. Assume the 11 kV grid behind it is perfectly stiff.
Full-load current on the 433 V side. I = S ÷ (√3 × V) = 250,000 ÷ (1.732 × 433) = 333 A.
Full-load current on the 11 kV side. 250,000 ÷ (1.732 × 11,000) = 13.1 A.
The factory test. With the low-voltage side shorted, only 4.5% of 11,000 V, which is 495 V, is needed on the high-voltage side to drive 13.1 A.
Fault current at the low-voltage terminals. 333 ÷ 0.045 = 7,410 A, about 22 times full load.
Fault level. 250 kVA ÷ 0.045 = 5.56 MVA.
Impedance in ohms, seen from the 433 V side. Z = 0.045 × 433² ÷ 250,000 = 0.0337 Ω per phase. Check: phase voltage 433 ÷ √3 = 250 V, and 250 ÷ 0.0337 = 7,410 A.
Change the impedance and the fault current moves the other way:
4% gives 333 ÷ 0.04 = 8,330 A.
5% gives 6,670 A.
A 6.25% unit of the same rating would give 5,330 A.
Is the impedance mostly resistance or reactance?
You can estimate the split from the same BIS table, which also lists the maximum total losses. For a 250 kVA unit at energy efficiency level 1, the limits are 980 W at 50% load and 2,930 W at 100% load. Copper loss goes as I², so it is four times larger at full load than at half load, while the core loss stays the same.
Copper loss at full load: (2,930 − 980) × 4 ÷ 3 = 2,600 W.
Core loss: 980 − 2,600 ÷ 4 = 330 W.
Resistance part: 2,600 ÷ 250,000 = 1.04%.
Reactance part: √(4.5² − 1.04²) = 4.38%.
So most of the 4.5% is leakage reactance. That is why a transformer's short-circuit current lags the voltage by a large angle. The size of the current, though, follows from the total impedance in the same way.
Why is the real fault current usually lower?
The 7,410 A figure assumes the 11 kV network behind the transformer has no impedance of its own. It does. Suppose, as an illustrative value, the 11 kV network can supply 250 MVA into a fault at that point. Seen from the 433 V side, that adds 433² ÷ 250,000,000 = 0.00075 Ω, and the current falls to 250 ÷ (0.0337 + 0.00075) = 7,250 A. The Rex Power note makes the same point: the simple formula holds when the transformer's impedance dominates.
The bigger reduction comes from the cable. A short circuit inside a house is at the end of tens or hundreds of metres of cable, whose resistance adds to the loop. That is why a fault near the transformer is far more severe than one at a distant house, and why breakers close to a transformer must be able to break much larger currents. How long a cable can carry such a current is worked in how long a house cable survives a short circuit.
Distribution transformers and the panels near them are live, high-energy equipment. Only the electricity utility's staff or a licensed electrician should work on or test them. This post gives no instructions for testing.
To review the ideal transformer and the turns ratio before working numbers like these, the transformer entries in the Concept Library explain each step.
Quick checklist
A transformer acts like an ideal transformer with a small series impedance, its "internal resistance".
Per-cent impedance: the voltage, as a percentage of rated, that drives full-load current with the output shorted.
Fault current = full-load current ÷ (per-cent impedance ÷ 100).
250 kVA, 433 V, 4.5%: 333 A full load, about 7,410 A into a short at the terminals.
Upstream network and cable impedance lower the real fault current.
Work on transformers is for utility staff or a licensed electrician only.