On this page
Cast epoxy and other solid insulation sometimes trap a small air bubble when they set. The solid around the bubble may be under a modest electric stress, yet the air inside the bubble starts to spark, again and again, every half-cycle of the supply. These tiny sparks are called partial discharges. Over time they damage the insulation. The reason the bubble sparks first is a Class 12 result: at a boundary between two dielectrics, the normal component of εE is the same on both sides, so the field jumps up in the material with the smaller dielectric constant.
What is a partial discharge?
The standard for measuring it, adopted in India as IS/IEC 60270, High-voltage test techniques: Partial discharge measurements, defines a partial discharge as a localised electrical discharge that only partially bridges the insulation between conductors. It notes that they come from local stress concentrations and last much less than a microsecond each. The size of a discharge is reported as an apparent charge, usually in picocoulombs (pC). The lowest applied voltage at which discharges appear is the partial discharge inception voltage.
Why is the field in a flat air void εr times stronger?
Take a flat void lying across the field, like a thin coin between two parallel electrodes. The field is perpendicular to its faces. There is no free charge on the boundary, only bound polarisation charge, so the normal component of the displacement D = εE is continuous:
ε₀ × E_void = ε₀εr × E_solid, which gives E_void = εr × E_solid
Air has εr close to 1. For the epoxy, take εr = 4 as a round, illustrative value; real resins vary with their filler. Then the field in a flat void is 4 times the field in the epoxy next to it.
It is the same idea as a dielectric slab reducing the field inside it, as in capacitance with a dielectric slab of thickness t. Here the "slab" is the solid, and the thin air gap is where the field is left high.
How do you find the field in the void and the solid?
Treat the stack as two capacitors in series: the solid of total thickness (d − t) and the void of thickness t. The applied voltage splits as
V = E_solid(d − t) + E_void × t = E_solid[(d − t) + εr t]
so E_solid = V/((d − t) + εr t) and E_void = εr V/((d − t) + εr t).
Worked example: a 0.5 mm void in 10 mm of epoxy
An epoxy insulator 10 mm thick sits between flat electrodes, with 20 kV (peak) across it. Take εr = 4. A flat void 0.5 mm thick lies across the field. All values are illustrative, not a real product.
No void. E = V/d = 20/10 = 2.0 kV/mm everywhere.
Field in the solid with the void. E_solid = 20/((10 − 0.5) + 4 × 0.5) = 20/11.5 = 1.74 kV/mm.
Field in the void. E_void = 4 × 1.74 = 6.96 kV/mm.
Check the voltages add up. 1.74 × 9.5 + 6.96 × 0.5 = 16.5 + 3.5 = 20 kV. Correct.
Air's breakdown in a 0.5 mm gap. A widely used empirical fit for uniform-field air at 20 °C and 1 atm is U_b = 6.72√d + 24.36d (kV, peak, d in cm), from the NPTEL high-voltage engineering notes on Paschen's law. With d = 0.05 cm: U_b = 6.72 × 0.224 + 24.36 × 0.05 = 1.50 + 1.22 = 2.72 kV, a field of 5.44 kV/mm.
Compare. The void carries 3.5 kV, its field is 6.96 kV/mm, and 6.96 > 5.44. The void breaks down. The epoxy, at 1.74 kV/mm, is at a stress solid insulation like this is designed to carry.
Inception voltage. Discharges start when E_void reaches 5.44 kV/mm: V_i = 5.44 × 11.5/4 = 15.6 kV peak.
Why does the air break down when the solid does not?
Two things work against the air. First, the field is εr times higher in it. Second, air is a weak insulator. A gas breaks down when electrons gain enough energy between collisions to ionise molecules and start an avalanche. Thin gaps need a higher field, because an electron has less distance in which to multiply. This is Paschen's law. The same NPTEL notes put air at about 31 kV/cm for a 1 cm gap, rising to about 92 kV/cm at 0.1 mm. In this insulator, a void thinner than about 0.17 mm would not discharge at 20 kV, by the same two formulas. Compare the door-handle shock, which uses the long-gap value.
The gas in a real void may not be at 1 atm, so treat 5.44 kV/mm as an estimate.
Does the shape of the void matter?
Yes, a lot. The factor εr is the upper limit, for a void flat across the field. For a spherical void, solving Laplace's equation gives a field inside of 3εr/(2εr + 1) times the field far away: 12/9 = 1.33 for εr = 4. A void stretched along the field gets almost no enhancement, because the tangential component of E is what stays continuous there. In the example, a spherical void of the same size would see about 2.7 kV/mm, and by the same rough estimate discharge would need about 41 kV. Flat voids and delaminations between layers are the ones to worry about.
Why do factories test cables and switchgear for it?
After each discharge, charge settles on the void walls and the field inside drops, until the supply voltage rises again on the next half-cycle. Each pulse is tiny, but they can repeat on every half-cycle, so at 50 Hz there can be a hundred or more each second. Peer-reviewed work on artificial voids in epoxy, for example Beca, Rowland and colleagues at IEEE CEIDP 2021, reports tracking and fractures in the resin caused by discharges in voids. That is why high-voltage cables, bushings and switchgear are given a partial discharge test before they leave the factory: the apparent charge is measured in pC to the method of IEC 60270, and the product standard sets the allowed level. The physics in this post is for understanding only. Never go near high-voltage equipment, substations or fallen lines; testing is done by trained engineers.
Practising this as a JEE problem
Layered-dielectric questions are standard JEE capacitor problems. If you want them worked step by step, the Fermi Problem Library has a step-by-step solver that explains the reasoning. For a wider plan, Fermi Test Prep offers personalised preparation for JEE Main & Advanced with an AI tutor, live classes, adaptive mocks, mentorship and a study plan that updates based on mastery.
Quick checklist
Partial discharge: a discharge that bridges only part of the insulation, measured in pC.
Normal to a boundary, D = εE is continuous, so E_void = εr E_solid for a flat void.
E_solid = V/((d − t) + εr t); check that the layer voltages add to V.
0.5 mm void in 10 mm epoxy at 20 kV: 1.74 kV/mm in the solid, 6.96 kV/mm in the void, above air's 5.44 kV/mm.
Spherical void: factor 3εr/(2εr + 1), only 1.33 for εr = 4.
Never approach high-voltage equipment.