Large buildings move air with fans in air-handling units, and many of them now run those fans through variable-speed drives instead of at a fixed speed. The reason is a short chain of physics. Flow goes up with fan speed, pressure goes up with speed squared, and power goes up with speed cubed. Run a fan at 80% speed and it draws only about half the power.
What are the fan affinity laws?
For one fan working on one fixed duct system, changing the shaft speed N changes the flow Q, the pressure rise Δp and the power P like this:
Q ∝ N
Δp ∝ N²
P ∝ N³
These are the fan laws (also called affinity laws). The US Department of Energy's fan sourcebook, written with the fan industry body AMCA, defines them as theoretical relationships "for a given fan used in a given fixed system", and states that speed has a linear relationship with airflow, a second-order one with pressure and a third-order one with power (US DOE and AMCA, Improving Fan System Performance: A Sourcebook for Industry). The same laws apply to centrifugal pumps.
Why does flow go as speed and pressure as speed squared?
Picture the air leaving the blade tips. The tip speed is 2πr × N, so it is proportional to N. Every air velocity in the fan scales with that tip speed, because the blade shape and the duct shape do not change.
Flow. Volume flow is area × velocity. The areas are fixed, so Q ∝ v ∝ N.
Pressure. The pressure a fan can build is of the order of a dynamic pressure, ½ρv². With v ∝ N, Δp ∝ N².
The ducts agree with this. In the DOE sourcebook, the pressure lost across each duct component goes as the square of the air velocity, so the whole system curve is a parabola through the origin (DOE sourcebook). If the fan's pressure and the system's pressure loss both scale as v², then after a speed change the new operating point is just a scaled copy of the old one.
Why does power go as speed cubed?
The air power is pressure rise × volume flow:
P_air = Δp × Q
Check the units: Pa × m³/s = (N/m²)(m³/s) = N·m/s = W. So the power is a product of something ∝ N² and something ∝ N, and P ∝ N³.
The electrical input is P = Q Δp / η, where η is the combined efficiency of fan, belt and motor. If η stays the same, input power also scales as N³.
This is the same cube you meet in the power a cyclist needs against air drag, and for a related reason: force ∝ v² multiplied by speed v. There, the cyclist moves through still air; here, the fan moves air through fixed ducts.
Worked example: an air-handling fan at three speeds
Take an illustrative air-handling fan: 10,000 m³/h against 500 Pa at full speed, with an overall efficiency of 65%.
Convert the flow. 10,000 m³/h ÷ 3600 s/h = 2.778 m³/s.
Air power at full speed. 2.778 × 500 = 1,389 W.
Input power at full speed. 1,389 / 0.65 = 2,137 W.
At 90% speed. Q = 0.9 × 10,000 = 9,000 m³/h. Δp = 0.9² × 500 = 405 Pa. P = 0.9³ × 2,137 = 0.729 × 2,137 = 1,558 W.
At 80% speed. Q = 8,000 m³/h. Δp = 0.64 × 500 = 320 Pa. P = 0.512 × 2,137 = 1,094 W, which is 51% of full power.
At 50% speed. Q = 5,000 m³/h. Δp = 0.25 × 500 = 125 Pa. P = 0.125 × 2,137 = 267 W, one eighth of full power.
Energy over a year. Running at 80% instead of 100% for 4,000 hours saves (2,137 − 1,094) W × 4,000 h = 4,171 kWh. At an illustrative tariff of ₹8 per kWh, that is about ₹33,000 a year from one fan.
The DOE sourcebook gives the same headline: by the fan laws, cutting speed by 20% cuts fan power by 50% (DOE sourcebook).
Why not just close a damper to cut the airflow?
A damper is a valve in the duct. Partly closing it adds resistance, so the system curve gets steeper and the flow drops. But the fan still spins at full speed and still works hard: it is now building pressure only for that pressure to be thrown away across the damper as heat and noise.
Slowing the fan does the opposite. It keeps the ducts as they were and simply moves the operating point down the same parabola. That is why the DOE sourcebook calls fan speed adjustment generally the most efficient way to control airflow (DOE sourcebook). Note that the affinity laws do not describe a damper-controlled fan at all, because its speed never changes.
When is the real saving smaller than the cube law?
Three things eat into the ideal N³.
Fixed pressure in the system. Some systems need a minimum pressure whatever the flow, for example to keep a set pressure at the far end of a duct. The DOE sourcebook notes that system curves can have such a static part. Suppose, for illustration, the system needs Δp = 150 Pa + 350 Pa × (Q/Q₀)². At 80% flow it needs 150 + 350 × 0.64 = 374 Pa, not 320 Pa. Power is then 0.8 × 374/500 = 60% of full, not 51%.
Motor and drive losses. Efficiency usually falls at low load, so η is not constant. The DOE sourcebook warns that motor efficiency and power factor can drop when speed is cut (DOE sourcebook).
A different system. The laws compare the same fan on the same ducts. Change the filters, ducts or blade angle and the comparison no longer holds.
Once the ducts are fixed, this is the same Q and Δp bookkeeping as pump power for lifting water to a tank, which works out power at one operating point. The affinity laws tell you how that point moves when the speed changes. A household ceiling fan regulator is a different matter: why a fan regulator gets warm is about where electrical energy is lost in the control itself.
To practise ratio problems like these, the Fermi Problem Library has a step-by-step solver that explains the reasoning, and the Concept Library covers pressure, flow and power in fluids.
Quick checklist
Same fan, same ducts: Q ∝ N, Δp ∝ N², P ∝ N³.
Δp ∝ N² because pressure scales with ½ρv² and every velocity scales with tip speed.
Power = Δp × Q; Pa × m³/s = W.
80% speed gives 64% pressure and 51.2% power; 50% speed gives 12.5% power.
Dampers cut flow but not speed, so they waste the pressure the fan makes.
Fixed system pressure and motor losses make real savings smaller than the cube.