Switch on a 400 km, 765 kV line from one end with nothing connected at the other, and the far end does not sit at 765 kV. It climbs to about 840 kV. This is the Ferranti effect (after the engineer Sebastian Ziani de Ferranti), and it is why long extra-high-voltage lines carry large reactors at their ends. This post works it out with the standard line data from India's Central Electricity Authority (CEA).
Why does the voltage rise at the open end of a long line?
Every kilometre of an overhead line has series inductance and shunt capacitance to ground. Even with no load connected, the capacitance draws current, because the line charges and discharges 50 times a second. This charging current has to flow through the line's own inductance.
Take the receiving-end voltage V_r as the phasor reference.
The charging current I_c is capacitive, so it is 90° ahead of V_r.
The voltage across an inductive reactance X is a further 90° ahead of its current, so the drop jX·I_c points at 180° to V_r.
Kirchhoff's law along the line gives V_s = V_r + jX·I_c. Because jX·I_c points opposite to V_r, the magnitudes subtract: V_s = V_r − X·I_c.
Turned around, V_r = V_s + X·I_c. The far end is higher than the sending end.
With a normal lagging load (motors, transformers) the drop across X lowers the voltage and the far end sags. The rise appears only at no load or very light load. If phasor addition is rusty, the post on AC circuits for JEE: phasors, impedance and resonance covers it.
What formula gives the far-end voltage?
A JEE way to see it: a series LC circuit with the output taken across C gives V_C/V = 1/(1 − ω²LC), more than 1 below resonance. A long line is many such sections in a row.
For the real, distributed line, take it as lossless with L and C per kilometre. Waves travel at v = 1/√(LC), and each kilometre shifts the phase by β = 2πf/v. For a line of length l, open at the far end:
V_r/V_s = 1/cos(βl)
For short lines this is about 1 + (βl)²/2, so the rise grows with the square of the length.
What are the line constants of an Indian 765 kV line?
The CEA Manual on Transmission Planning Criteria (2023), Table I(a) gives standard data for a 765 kV single-circuit line with four ACSR Bersimis sub-conductors per phase: X = 4.880 × 10⁻⁵ pu and B = 2.35 × 10⁻² pu, per km per circuit on a 100 MVA base. The base impedance is 765²/100 = 5,852 Ω, so:
Reactance X = 4.880 × 10⁻⁵ × 5,852 = 0.286 Ω/km, so L = X/(2π × 50) = 0.909 mH/km.
Susceptance B = 2.35 × 10⁻² ÷ 5,852 = 4.02 µS/km, so C = B/(2π × 50) = 12.8 nF/km.
Wave speed v = 1/√(LC) = 293,000 km/s, a little under the speed of light.
Wavelength at 50 Hz: v/f = 5,870 km.
Surge impedance √(L/C) = 267 Ω.
These are planning values; the manual says real tower data should be used where available, so treat the results below as estimates. The four-wire bundle that sets them is covered in why 765 kV lines use bundles of wires.
Worked example: how high does a 400 km line go?
A 400 km, 765 kV line is energised from one end with the far end open. Find the far-end voltage, the charging current, and the effect of a 330 MVAr reactor at the far end.
Electrical length. βl = 2π × 50 × 400 ÷ 293,400 = 0.428 rad = 24.5°.
Voltage ratio. cos 24.5° = 0.910, so V_r/V_s = 1/0.910 = 1.099.
Far-end voltage. V_r = 765 × 1.099 = 841 kV, about 10% high.
Check the estimate. 1 + (0.428)²/2 = 1.092, a 9.2% rise: close, but slightly low.
Compare with the limit. The same CEA manual sets the normal maximum for a 765 kV system at 800 kV (1.05 pu). The open end is 41 kV over.
Charging current. The phase voltage is 765/√3 = 441.7 kV. I_c ≈ ωClV = 2π × 50 × 12.78 × 10⁻⁹ × 400 × 441,700 = 709 A per phase. Three-phase reactive power: √3 × 765 kV × 709 A ≈ 940 MVAr. The exact sending-end value is a little higher, about 756 A.
Add a reactor. The manual lists 110 MVAr single-phase units as a standard 765 kV reactor size, so a bank of three gives 330 MVAr, a reactance of 765²/330 = 1,773 Ω per phase. With the reactor at the open end, the lossless line result is V_s = V_r[cos βl + (Z_c/X_sh) sin βl] = V_r[0.910 + (267/1,773) × 0.415] = 0.972 V_r.
New far-end voltage. V_r = 765 ÷ 0.972 = 787 kV, now under the 800 kV limit.
Step 7 uses a result beyond NCERT: the reactor draws a lagging current that cancels part of the charging current, so less current flows through the line's inductance.
How does the rise grow with line length?
With the same constants:
200 km: 1.023 (2.3% high)
400 km: 1.099 (9.9% high)
800 km: 1.53
1,000 km: 2.09
1,467 km: a quarter wavelength, where cos(βl) = 0 and the lossless formula goes to infinity
The quarter-wave case is a resonance of the distributed line, like the fundamental of a pipe closed at one end. Losses keep a real line finite. A single lumped section, with the line's total L and half its C at the open end (the nominal-π model), gives 1/(1 − ω²LCl²/2) = 1.101 at 400 km against 1.099, but drifts away for longer lines.
What do grid engineers do about the Ferranti effect?
Shunt reactors. The CEA manual says line reactors may be provided if an EHV line cannot be charged without exceeding the maximum voltage limits. Bus reactors at substations hold the voltage down at light load.
Lower the charging voltage. The manual also asks planners to consider reducing the voltage at the end used to charge the line before adding reactors. Since the rise is a ratio, a lower V_s gives a lower V_r.
Cables hit the problem sooner. Cables have far more capacitance per kilometre than overhead lines, which is why long sea crossings use DC, as explained in why long undersea power cables use DC.
The Ferranti effect is a steady rise at 50 Hz, not a switching or lightning surge.
If phasors are hard to picture, the Fermi Simulation Lab has interactive simulations for ideas easier to see than read. For more phasor problems, the Fermi Problem Library has a step-by-step solver that explains the reasoning.
Quick checklist
A long line has series L and shunt C; at no load the charging current flows through L.
The drop across X from a capacitive current adds to V_r, so V_r > V_s.
Lossless line: V_r/V_s = 1/cos(2πfl/v), with v = 1/√(LC).
CEA 765 kV data: L ≈ 0.909 mH/km, C ≈ 12.8 nF/km, v ≈ 293,000 km/s.
400 km at 765 kV: about 841 kV open-ended, against an 800 kV limit.
Shunt reactors absorb the charging current and pull the voltage back down.