A voltage stabiliser that turns a sagging 180 V into 230 V for your fridge is a transformer, but not the kind in your textbook. It has one winding with taps on it, not two separate windings. That single change means only part of the power is actually transformed; the rest flows straight through the copper. For a boost from 180 V to 230 V, the transformed part is about a fifth of the load, so the winding can be about a fifth of the size. This post shows why, with the currents worked out in each part of the winding.
What is an autotransformer?
An ordinary transformer has two windings on one core, with no electrical connection between them. Its turns ratio sets the voltage ratio, V₂/V₁ = N₂/N₁, as covered in the transformer turns ratio simulation.
An autotransformer has one winding on the core, with a connection (a tap) part-way along it. The same rule holds, because every turn links the same flux, so the voltage per turn is the same along the whole winding. If the supply goes across 180 turns' worth of the winding and the load across 230 turns' worth, the output is 230 V for a 180 V input.
Do stabilisers really use one? V-Guard's own buying guide (V-Guard, Voltage Stabilizer Buying Guide) says its stabilisers use electronic circuitry that changes the taps of an inbuilt auto transformer with electromagnetic relays. Why low voltage harms a fridge compressor in the first place is explained in why fridges need a voltage stabiliser. Here we look only at the transformer inside.
How does current flow in an autotransformer?
Split the winding into two parts:
Common part: from the bottom of the winding to the 180 V tap. Both the supply and the load share it.
Series part: from the tap to the top, adding the extra 50 V. Only the load current flows here.
At the tap, the supply current comes in and the load current goes out. The common part carries only the difference. This is the whole trick: the two currents in the common part flow in opposite directions, so they mostly cancel.
The ampere-turns must balance, as in any ideal transformer: the series part's turns times its current equals the common part's turns times its current. That check is done in the worked example below.
Worked example: a 1,000 VA stabiliser boosting 180 V to 230 V
Take an ideal autotransformer delivering 1,000 VA at 230 V from a 180 V supply. These are round illustrative values.
Load current. I_out = 1,000 ÷ 230 = 4.35 A.
Supply current. With no losses, input VA equals output VA: I_in = 1,000 ÷ 180 = 5.56 A.
Series part. It carries the load current, 4.35 A, across 50 V: 50 × 4.35 = 217 VA.
Common part. It carries the difference, 5.56 − 4.35 = 1.21 A, across 180 V: 180 × 1.21 = 217 VA.
Ampere-turn check. Turns are proportional to voltage, so compare 50 × 4.35 = 217 with 180 × 1.21 = 217. They match, so the core's flux from the two parts balances.
Compare. A two-winding transformer doing the same job would need a 1,000 VA primary and a 1,000 VA secondary. Each part of the autotransformer handles only 217 VA, which is 21.7% of the load.
In general, the transformed share is
transformed share = 1 − V_low/V_high
Here 1 − 180/230 = 0.217. The other 78.3% of the power is conducted straight through from supply to load.
Why is the saving large only when the voltages are close?
The formula answers this at once.
Stabiliser at the edge of its range. V-Guard's brochure (V-Guard stabilisers) lists fridge models with a working range of 130 V to 290 V. Boosting 130 V to 230 V gives a transformed share of 1 − 130/230 = 43%, and the supply current rises to 1,000 ÷ 130 = 7.7 A for the same 1,000 VA. A wider range needs a bigger winding.
Power grid. POWERGRID's tender documents (POWERGRID transformer package) specify 500 MVA, 400/220/33 kV three-phase auto-transformers. For 400 kV to 220 kV, the share is 1 − 220/400 = 45%, so only about 225 MVA of a 500 MVA unit is transformed.
A big step-down. Going from 230 V down to 12 V, the share would be 1 − 12/230 = 95%. There is almost no saving, and the output would still be tied to the mains.
Less copper and a smaller core also mean smaller copper and iron losses, the losses described in energy losses in a transformer.
How does a variac give a smooth 0 to 260 V?
A variac (variable autotransformer) in a school or college lab is the same idea with a sliding contact. The winding is wound on a ring-shaped (toroidal) core, and a carbon brush slides over the bare turns, so the output can be picked off anywhere along the winding. Noratel's catalogue (Noratel Vario transformers) lists toroidal autotransformers rated 230 V in, 0–260 V out. The winding extends about 30 V beyond the input connection, so the brush can also give a little more than the supply.
Why does an autotransformer give no isolation?
Because there is one winding, the output is connected to the supply. In a two-winding transformer the secondary has no wire connecting it to the mains; in an autotransformer it does. So the output of a stabiliser or variac is as dangerous to touch as the mains itself, even when the dial is turned down to a few volts. In a step-down autotransformer there is a further risk: if the common part of the winding breaks, the full input voltage can appear across the load.
If you want more transformer problems with the reasoning shown, the Fermi Problem Library has a step-by-step solver that explains the reasoning.
Quick checklist
One winding with a tap; V₂/V₁ = N₂/N₁ still holds.
The common section carries I_in − I_out; the series section carries I_out.
Transformed share = 1 − V_low/V_high: 22% for 180 → 230 V, 43% for 130 → 230 V.
The saving is large only when the two voltages are close.
Grid 400/220 kV units are autotransformers; 45% of their power is transformed.
No isolation: the output is connected to the mains.